Continuous Power: 260 kW DC Operating Range: 295 V - 500 V Peak Efficiency: 97.7%
Continuous Power: 260 kW DC Operating Range: 265 V -500 V Peak Efficiency: 97.7%
The PV Powered™ 260 kW model has raised the bar once again for commercial inverter reliability, ease of installation, and lifetime maintainability. High reliability is enabled by market-leading features, including:
- Bus bar power connections
- The widest temperature rating of any inverter in its class
PVP260kW data sheet
|
The highly integrated system saves installers time and money by including load-rated AC & DC service disconnects, neutral-free installation, oversized bus bar landings, and generous cable bending area for top, bottom, and side cable entry options.
The PVP260kW inverter has a standard 295 VDC minimum MPPT and an optional full power 265 VDC minimum MPPT—the lowest MPPT voltage of any commercial inverter in the industry. This low input voltage option enables exceptional stringing capability with all PV module technologies, including new-thin film modules.
The PVP260kW model also simplifies performance monitoring by offering inverter-integrated solutions from market leaders Fat Spaniel, Draker, and Energy Recommerce. Additional options from PV Powered include integrated revenue-grade meter and sub-combiner monitoring. PV Powered backs all its commercial inverters with an industry-leading 10-year warranty and an unprecedented optional 20-year warranty, plus the best service and support team in the business.
- Redundant cooling system with Smart Air Management™
- Low parts count reduces potential failure points
- Engineered bus bar power connections
- Card cage circuit board system minimizes electronic interconnections
- Top, bottom, and side entry with generous bending area and oversized bus bar landings
- Large DC sub-combiner compartment with multiple fuse options
- Full power output at 265 VDC enables more PV array design options
- Exterior mounting flanges for fast and easy anchoring with no pre-drilling
- All maintenance and service via front access
- Fast change circuit board system shortens service time
- Load-rated AC and DC service disconnects
|
Model
|
260kW
|
260kW-LV
|
| Continuous Power Output (kW) |
260 kW |
260 kW |
| Weighted CEC Efficiency (%) |
97.0% |
96.5% |
| Maximum DC Input Voltage (VOC) |
600 |
600 |
| DC Peak Power Tracking Range (V) |
295 – 500 |
265 - 500 |
| DC Imp Nominal Current (A) |
918 |
1022 |
| AC Nominal Voltage (V) |
480 |
480 |
| AC Operating Range (V) |
422 - 528 |
422 - 528 |
| AC Frequency Range (Hz) |
59.3 - 60.5 |
59.3 - 60.5 |
| AC Maximum Continuous Current (A) |
316 |
316 |
| Standby Losses (W) |
67 |
67 |
| Harmonic Distortion (%THD) |
<3% |
<3% |
| Power Factor |
>.99 |
>.99 |
|
Model
|
260kW
|
260kW-LV
|
| Enclosure |
NEMA 4 |
NEMA 4 |
| Construction |
Powder Coated Steel |
Powder Coated Steel |
| Mounting |
Pad Mount |
Pad Mount |
| Weight (lbs) |
5,000 |
5,000 |
| Cooling |
Forced Convection |
Forced Convection |
| Temperate Range (ºC) |
-30 to 50 |
-30 to 50 |
| Isolation Transformer |
Yes |
Yes |
UL 1741, IEEE519, IEEE929, IEEE1547
FCC Class A for conducted and radiated